Three Phase Multi-channels Power Meter
Specifications
1.Din sliding-way mounting2.Modbus-RTU protocol
3.Harmonics measurement
4.+kW,-kW,+kVar,-kVAR
5.With LCD display
|
YD2060-J Series Multi-channels Intelligent Power Analyzer YD2060-J series multi-channels intelligent power analyzer is a high-performance meter with the measurement functions needed by monitoring multi-channels electric equipment. It can read the measuring value of parameters, such as current, voltage, power, power factor etc. in each loop through the communication with single-line LCD display. There are 8 models of YD2060-J series multi-loops intelligent power analyzer for selection: YD2060-J, YD2060-J2, YD2060-JK, YD2060-J2K. |
|
Application Ø DIN sliding-way mounting Ø Electric energy consumption monitoring Ø Remote measuring all kinds of the electric parameters |
|
Features Ø ModbusRTU & DL/T645-1997 double protocol Ø Computating the current active energy in each ciruit Ø Measuring voltage and current in each circuit Ø Measuring forward & reverse, active & reactive power of each circuit Ø Measuring power factor in each circuit Ø Measuring frequency Ø With date and time Ø ModbusRTU and DL/T645-1997 protocol |
Model |
Description |
Note |
YD2060J |
Three-phase voltage, frequency in one circuit, each phase current, power, power factor, energy in three circuits. |
|
YD2060-J2 |
Three-phase voltage, frequency in one circuit, each phase current, power, power factor, energy in four circuits. |
|
YD2060-JK |
Three-phase voltage, frequency in one circuit, each phase current, power, power factor, energy in three circuits. |
With split-type transformer |
YD2060-J2K |
Three-phase voltage, frequency in one circuit, each phase current, power, power factor, energy in four circuits. |
With split-type transformer |
|
|
Type of transformer for selection |
CT20 |
5A/10mA |
Close-type transformer |
||
50A/10mA | ||||||
100A/20mA |
||||||
CT19 |
50A/10mA |
Split-type transformer |
||||
100A/20mA |
||||||
200A/40mA |
||||||
300A/60mA |
||||||
400A/80mA |
||||||
Electrical Characteristics | ||||||
Measuring Characteristics |
Multi-loops three-phase AC power monitoring |
|||||
Type of transformer |
close-type |
split-type |
||||
Measuring Accuracy |
Current |
0.5% |
1.0% |
|||
Voltage |
0.5% |
0.5% |
||||
Power, power factor |
1% |
2% |
||||
Frequency |
0.1% |
0.1% |
||||
|
Active energy |
1% |
2% |
||||
Input voltage characteristics |
Range |
Input: 0~600V/AC (direct L-L) |
||||
|
Measuring: 30~600V/AC(direct L-L) 20~400V/AC(direct L-N) | ||||||
Input power consumption |
≤1VA |
|||||
Frequency measuring range |
45~60Hz |
|||||
|
Input current characterstics Matched 5A/10mA transformer |
Range |
Input: 0~5A |
||||
Measuring: 10mA~6A | ||||||
Max.overload |
Continuous current 10A |
|||||
|
Input power consumption |
≤1VA |
|||||
|
Input current characterstics (Ib/Io)50A/10mA~400A/80mA transformer |
Range |
Input: 0~Ib |
||||
Measuring: 0.004Ib~1.2Ib | ||||||
Max.overload |
Continuous current 2Ib |
|||||
|
Input power consumption |
≤1VA |
|||||
Auxiliary power supply |
DC power supply |
DC18~90V |
||||
|
AC / DC power supply |
AC 85~265V/DC85~330V (optional) |
|||||
|
Power consumption |
≤5VA or ≤2W
|
|||||
Send Inquiry to This Supplier
You May Also Like
-
Instrument TransformerNegotiableMOQ: 2500 Pieces
-
Wholesales Popular Laser Security Beam SensorNegotiableMOQ: 1 Set
-
LuminometersNegotiableMOQ: 1000 Pieces
-
Gradiometer, Gradient MeterNegotiableMOQ: 1 Piece
-
Aluminium Tripod For Total Station SDI006NegotiableMOQ: 1 Piece
-
Automotive TachometerUS$ 10 - 1,000MOQ: 50 Sets
-
Simiconductor TesterUS$ 750.00 - 750.00MOQ: 1 Set
-
Square Type Moving Coil Power Factor MeterNegotiableMOQ: 1000 Pieces
-
Split Core Current Transducer DCT24-300AAC/4-20mA DC OutputUS$ 8 - 10MOQ: 1 Piece
-
Benchtop Conductivity MeterDDSJ-308A/F/DDS-307NegotiableMOQ: 1 Unit