DN20 Ultrasonic Flowmeter is Used for Heating System Testing RS485 Communicating Junctions
TUF-2000 has an isolated serial port, the RS485.
TUF-2000 can support more than 4 different communication protocols by the same time; include MODBUS-ASCII, ASCII-RTU, Meter-BUS, the Fuji Extended Protocol and more than 10 compatible communication protocols used by Huizhongs flow meters.
MODBUS is a very commonly used industrial protocol. Both the RTU and the ASCII format of MODBUS is supported
The Fuji Extended Protocol is developed based on the protocol used in a Japanese ultrasonic flow meter. It is totally compatible with that of Version 7 flow meter.
TUF-2000 can be used as a sample RTU terminal. The 4-20mA output in the TUF-2000 can be used to open an analog proportional valve; The OCT output can be used to control the turn-on and turn-off of other devices such as a pump. The analog input can be used to input pressure or temperatures signals.
There is a programmable device address (or ID number) located at window M46. When TUF-2000 is used in a network, all the parameters of the flow meter can be programmed through the network, except the device address that needs the keypad.
At most occasions, data should be obtained by polling the flow mete with a command, the flow meter will respond with what the master asks.
TUF-2000 can also set to automatically output data at a period which is programmable.
The TUF-2000 also has a special command sets to facilitate the use of the flow meter in a GSM network.
REGISTER |
NUMBER |
VARIABLE NAME |
FORMAT |
NOTE |
0001-0002 |
2 |
Flow Rate |
REAL4 |
Unit: m3/h |
0003-0004 |
2 |
Energy Flow Rate |
REAL4 |
Unit: GJ/h |
0005-0006 |
2 |
Velocity |
REAL4 |
Unit: m/s |
0007-0008 |
2 |
Fluid sound speed |
REAL4 |
Unit: m/s |
0009-0010 |
2 |
Positive accumulator |
LONG |
Unit is selected by M31, and depends on totalizer multiplier |
0011-0012 |
2 |
Positive decimal fraction |
REAL4 |
Same unit as the integer part |
0013-0014 |
2 |
Negative accumulator |
LONG |
Long is a signed 4-byte integer, lower byte first |
0015-0016 |
2 |
Negative decimal fraction |
REAL4 |
REAL4 is a format of Singular IEEE-754 number, also called FLOAT |
0017-0018 |
2 |
Positive energy accumulator |
LONG |
|
0019-0020 |
2 |
Positive energy decimal fraction |
REAL4 |
|
0021-0022 |
2 |
Negative energy accumulator |
LONG |
|
0023-0024 |
2 |
Negative energy decimal fraction |
REAL4 |
|
0025-0026 |
2 |
Net accumulator |
LONG |
|
0027-0028 |
2 |
Net decimal fraction |
REAL4 |
|
0029-0030 |
2 |
Net energy accumulator |
LONG |
|
0031-0032 |
2 |
Net energy decimal fraction |
REAL4 |
|
0033-0034 |
2 |
Temperature #1/inlet |
REAL4 |
Unit: C |
0035-0036 |
2 |
Temperature #2/outlet |
REAL4 |
Unit: C |
0037-0038 |
2 |
Analog input AI3 |
REAL4 |
|
0039-0040 |
2 |
Analog input AI4 |
REAL4 |
|
0041-0042 |
2 |
Analog input AI5 |
REAL4 |
|
0043-0044 |
2 |
Current input at AI3 |
REAL4 |
In unit mA |
0045-0046 |
2 |
Current input at AI3 |
REAL4 |
In unit mA |
0047-0048 |
2 |
Current input at AI3 |
REAL4 |
In unit mA |
0049-0050 |
2 |
System password |
BCD |
Writable。00H for unlock |
0051 |
1 |
Password for hardware |
BCD |
Writable。“A55Ah” for unlock |
0053-0055 |
3 |
Calendar (date and time) |
BCD |
Writable。6 Bytes of BCD stands SMHDMY,lower byte first |
0056 |
1 |
Day+Hour for Auto-Save |
BCD |
Writable。For example 0512H stands Auto-save on 12:00 on 5th。0012H for 12:00 on everyday。 |
0059 |
1 |
Key to input |
INTEGER |
Writable |
0060 |
1 |
Go to Window # |
INTEGER |
Writable。 |
0061 |
1 |
LCD Back-lit lights for number of seconds |
INTEGER |
Writable。In unit second |
0062 |
1 |
Times for the beeper |
INTEGER |
Writable。Max 255 |
0062 |
1 |
Pulses left for OCT |
INTEGER |
Writable。Max 65535 |
0072 |
1 |
Error Code |
BIT |
16bits, see note 4 |
0077-0078 |
2 |
PT100 resistance of inlet |
REAL4 |
In unit Ohm |
0079-0080 |
2 |
PT100 resistance of outlet |
REAL4 |
In unit Ohm |
0081-0082 |
2 |
Total travel time |
REAL4 |
In unit Micro-second |
0083-0084 |
2 |
Delta travel time |
REAL4 |
In unit Nino-second |
0085-0086 |
2 |
Upstream travel time |
REAL4 |
In unit Micro-second |
0087-0088 |
2 |
Downstream travel time |
REAL4 |
In unit Micro-second |
0089-0090 |
2 |
Output current |
REAL4 |
In unit mA |
0092 |
1 |
Working step and Signal Quality
|
INTEGER |
The high byte is the step and low for signal quality,range 00-99,the larger the better. |
0093 |
1 |
Upstream strength |
INTEGER |
Range 0-2047 |
0094 |
1 |
Downstream strength |
INTEGER |
Range 0-2047 |
0096 |
1 |
Language used in user interface |
INTEGER |
0 : English,1:Chinese Other language will be supported later |
0097-0098 |
2 |
The rate of the measured travel time by the calculated travel time. |
REAL4 |
Normal 100+-3% |
0099-0100 |
2 |
Reynolds number |
REAL4 |
|
Kaifeng PuSheng instrument co., LTD., mainly producing all kinds of rotor meter, the level of spiral meter, vertical spiral water meter, water meter, prepaid intelligent water meter, IC card intelligent water meter, bluetooth intelligent water meter, nb intelligent water meter intelligent water meter and valve control meter, such as photoelectric read-only meter, ultrasonic heat meter, ultrasonic water meter, electromagnetic flowmeter, the throttle device, the vortex street flowmeter, Turbine flowmeter, and related software and hardware development, the company has intelligent circuit board and software research and development capabilities, through the ISO9000 certification system is a collection of research and development, production, sales, after-sales service, technical training as one of the high-tech production and development enterprises.
With decades of experience in the production and service of water meters, electricity meters and other meters and calibration devices, we have the best quality control experts and scientific research and production team in China. Company measurement experts get the measurers through certificate issued by the state in 1982, the quality control experts in 1968 (the original 983 factory), now known as artisans power of the luoyang bearing factory equipment factory work, presided over many products to participate in the national competition for weighing apparatus in China the national front row, computer industry core expert team with 20 years of experience, double card master, And scientific research institutes, universities, as well as a number of master's doctor cooperation to set up a RESEARCH and development service team, with various aspects of the system of research and development and production capacity, flow meter by decades of experience in the flow meter technical experts carefully built supervision. We service clients with unit of former five machine department, Beijing, Shanghai, ningbo and other places, shanxi, shandong, hebei, etc all kinds of users throughout the country, dozens of tap water company, we have training of luoyang, zhengzhou city tap water company check personnel, we have decades of instrument technical service and technical support capabilities.
Send Inquiry to This Supplier
You May Also Like
-
Tuf2000 Ultrasonic Water Flow Meter Clamp on Sensor Module Flow MeterUS$ 135 - 149MOQ: 1 Set
-
Hand-held Ultrasonic Flowmeter Professional Detection of Water Quality and PressureUS$ 300 - 490MOQ: 1 Set
-
Ultrasonic Flowmeter for Water Quality Monitoring and Temperature DetectionUS$ 419 - 425MOQ: 1 Set
-
DN40 Ultrasonic Heat Meter RS485 Communication Protocol ModBus Port ConnectionUS$ 35 - 46MOQ: 1 Set
-
Mechanical Cast Iron DN25 Digital Water Meter Meter is Used for Industrial Water Meter and Residential Water MeterUS$ 6 - 11MOQ: 1 Set
-
3 Inches Detachable Mechanical Water Flow Meter DN80 Woltman Water MeterUS$ 207 - 266MOQ: 1 Set
-
DN15 Mechanical Water Meter Professional Production and SalesUS$ 13.6 - 15.1MOQ: 1 Set
-
Lorawan NB-iot Smart Ultrasonic Water Meter for Residential Buildings Water MeterUS$ 35 - 46MOQ: 1 Set
-
Dn15 Water Meter System Digital Smart IC Card Prepaid Water Meter With Software Smart Brass BodyUS$ 25.8 - 46MOQ: 1 Set
-
Factory Price DN15 Prepaid Smart Card Water Meter With Software Flow MetersUS$ 25.8 - 36MOQ: 1 Set